Permit: T09OT02769

Parcel: 10711199A


Addresses:

3032 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/11/2010 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
01/08/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RECEPTACLE AT NORT OUTSIDE NEEDS TO IN OUTDOOR RATED BOX.
2. SECURITY LIGHTING NOT TO CODE
3. DEAD ENDED WIRING INSIDE NEEDS TO BE IN APPROVED BOX & COVER.
4. SEE NOT #3 LAST INSPECTION
01/05/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE
2) NO EXPOSED CABLES FOR RECEPTS AND CEILING FANS MUST BE COMPLETE RACEWAY WITH APPROVED CONNECTORS
3) EXTERIOR RECEPTS TO BE GFI PROTECTED IN APPROVED BOX AND COVER RATED FOR OUTDOOR USE
4) OUTSIDE SECURITY LIGHTING NOT PER CODE, ALSO WIRING ABOVE FRONT ENTRY ROOF
5) MISSING SWITCH COVER AT FRONT PORCH ENTRY