Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T09OT02644
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2010 | SIGN ELECTRIC | Approved | IVRS - Inspection :* 1) OK MONUMENT SIGNS |
|
12/22/2009 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :* 1) ENCASEMENT IS 2" MINIMUM-TOP, SIDES AND BOTTOM 2) OK TO ENCASE |
|
12/21/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SOUTH MONUMENT: 1) RACEWAY TO BE PER 501.15 (B) (2) 2) ENCASE CONDUITS NOT PER 300.5 3) FINISH MAKE UP AND GROUND BOX NORTH MONUMENT: 1) ENCASE CONDUITS NOT PER 300.5 |