Permit: T09OT02635

Parcel: 10711091A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/16/2009 FIRE - FINAL Approved Approved 12/16/09.
12/10/2009 FIRE - FINAL Denied Not approved 12/10/09.
1.) The area requires two exits with exit signs that are reqiuerd to be illuminated at all times.
2.) Need emergency back-up lighting for both exits.
3.) Need to remove the cross-bar security device from the rear exit.
4.) Only the main exit door can have a keyed locking device. all other doors must be readily openible without the use of a key.