Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT02554
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2009 | FIRE - FINAL | Approved | Approved 12/17/09. | |
12/11/2009 | FIRE - FINAL | Denied | Not approved 12/10/09. 1.) Emergency back-up light is burnt out. 2.) Need the updated annual fire alarm inspection report. |
|
12/01/2009 | FIRE - FINAL | Denied | Not approved 12/1/09. 1.) A-3 occupancies with an occupant load of 300> must have panic hardware on all exterior exit doors. 2.) Flush bolts are not permitted. 3.) Repair burnt out exit lights. 4.) Repair burnt out emergency back-up lights. 5.) Need the updated annual Fire Alarm inspection report. 6.) Any ROMEX wiring 7 feet and below to floor must be protected according to the electrical code. SW corner of main floor. 7.) The support stand for the A/C unit located in the utility room is unsafe. Provide strudy, permanent support for A/C unit. ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ |