Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2010 | FIRE - FINAL | Approved | Approved 6/16/10 | |
| 11/27/2009 | FIRE - FINAL | Denied | Not approved 11/25/09. 1.) Need address numbers for the building. 12 inch minimum. 2.) The frone security door must bo locked in the OPEN position when building is occupied. 3.) Secure front porch light. 4.) Only approved adaptors are allowed for use. 5.) Extension cords are for temporary use only. 6.) All permanent electricasl must meet the electrical code. 7.) Accumulation of weeds and dried grass in the fenced area to the rear must be cleared/cleaned and maintained at all times. 8.) A clear working asrea must be maintained around the electrical panel |