Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | FIRE - FINAL | Approved | ||
| 12/02/2009 | FIRE - FINAL | Denied | Need panic hardware on doulble doors southside. Need to repair flow alarm on kitchen sprinkler system. |
|
| 11/18/2009 | FIRE - FINAL | Denied | Remove slide bolt locks on front door only approved locking devices allowed. Remove slide bolt locks from all exit doors with panic hardware, only panic hardware is allowed. Double doors on south wall shall swing outward and have panic hardware installed or remove doors and install window back to original plans. Hood system needs up to date inspection done and maintain proper coverage. Exit signs shall be repaired or replaced all failed to work. Battery back lighting shall be repaired or replace all failed to work. Plans show front of building as a porch, owner wants to use as a patio for dinning needs approval first from DSC. Sprinkler system in kitchen only, needs repaired bell keeps ringing when breaker turned on, system can be removed but will need to send a letter to fire department asking for approval before removing. Wiring below 7' shall be protected in conduit, wire to TV on south wall. |