Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T09OT02385
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2010 | FIRE - FINAL | Denied | 1. Address must be displayed per Pima County requirerments (gave copy of requirements to property rep.} 2. Sign reqired on front door: THIS DOOR TO REMAIN OPEN WHEN BUILDING IS OCCUPIED. 3. Relocatable power taps shall be directly connected to a permanent power supply. 4. Extension cords shall not be substituted for permanent wiring. 5. Service/repair rear emergency egress light. 6. Replace rear door key lock with thumb turn dead bolt. 7. Electrical blanks and cover plate required on electrical service by rear door. 8. Portable fire extinguisher shall be serviced, mounted or removed. |