Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2009 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 11/04/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DISCONNECTS TO BE EXTERNAL OF SIGN NEC 600.6 2) VERIFY LISTING LABELS AND MANUFACTURES LABEL 3) SEAL OPEN KNOCKOUTS JUNCTION BOX 4) STRAP MC CABLE WITHIN 12" OF BOXES |
|
| 10/29/2009 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
| 10/27/2009 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |