Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2009 | FIRE - FINAL | Approved | Approved | |
| 10/14/2009 | FIRE - FINAL | Denied | 1.) Provide approved, accurate floor plans to include addition of rooms, walls and outside metal awning. 2.) Provide a readily visible sign over the main double doors that read," DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED" 3.) Repair /replace broken glass on front doors. 4.) Replace all missing cover plates. 5.) Provide thumb-turn locks to the doors leading into the main showroom area. 6.) Secure the integrity of the large rool-up glass doors in front of building. 7.) Cover all openings in walls and ceilings. 8.) Provide a thumb-turn lock for door leading into the office from the shop area or provide a sign for that door reading."NOT AN EXIT". 9.) Remove slide-bolt and pad lock from outside bathroom doors. 10.) Remove the side-bolt from the rear exit door. 11.) Need a breaker blank, outside electrical panal. 12.) Remove the EXIT sign located next to the metal rool-up door, back side of building. 13.) Cube adaptors are prohibited. |