Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T09OT02023
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2009 | FIRE - FINAL | Denied | 1.) Multiple misuse of extension cords. Cords are to be for temporary use only. 2.) Only approved adaptors are allowed for commercial use. 3.) Need the annual sprinkler inspection report. 4.) Need the 5 year internal check valve inspection report. 5.) Replace all missing ceiling tiles. 6.) Spiced electrical wiring is prohibited. 7.) Need a splash guard between the fryer and open flame appliance. 8.) Need the 6 month hood inspection report. 9.) Need a sprinkler head guard in cooler araea. 10.) Need a "K" type fire extinghuisher for the kitchen. 11.) Need a breaker blank for electrical panel. 12.) Emergency back-up light in the kitchen area next to the exit is burnt out. 13. ) Must maintain at least one of the patio double gate doors locked in the open position when the building is occupied. |