Permit: T09OT01885

Parcel: 11627504B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09OT01885

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2009 FIRE - FINAL Approved
09/09/2009 FIRE - FINAL Denied 1.) Need "NOT AN EXIT" for SW door located next to fire place. Main dining area.
2.) Need thumb-turn locks for the doors in the:
a.) snack bar area.
b.) wine room.
c.) office in kitchen area.
3.) Repair or cover any holes or openings in walls.
4.) Extension cords are to be for temtporary use only.
5.) Secure the piping under kitchen hood.
6.) Confirm proper coverage for 6 burner range. (back-shelf)
7.) Lable locations for "K" extinguishers.