Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2009 | FIRE - FINAL | Approved | ||
| 09/15/2009 | FIRE - FINAL | Denied | Replace sprinkler head front canopy, with orange spray foam on it. Don't clean it replace it. Call back on final when finished painting and exit signs are back in place and sprinkler heads are uncovered. |
|
| 08/31/2009 | FIRE - FINAL | Not ready for Inspection | Patch all holes in Hot water room. Correct sprinkler coverage in swan entrance area, storage room for supplies blocking spray coverage. Need hood inspection done this is done every 6 months. Need yearly sprinkler inspection done, last inspection on file 07/2008. Keep all stock down below 18" from all sprinkler heads. Front door needs to open outward for the occupant load of 103. Remove table from front of door in kitchen. |
|
| 08/27/2009 | FIRE - FINAL | Not ready for Inspection |