Permit: T09OT01778

Parcel: 121113250


Addresses:

4825 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09OT01778

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2009 FIRE - FINAL Approved
09/03/2009 FIRE - FINAL Denied 1.) Need emmergency back-up light for 2nd required exit.
2.) The 2 existing emergency back-up lights are burnt out.
3.) Door men's bathroom sticks, hard to open.
4.) Kitchen hood is past due for the 6 momth inspection. (last inspection in 2007)
5.) "K" type extinguisher for kitchen is missing.
6.) Grease build up on hood must be cleaned. Provide document of last cleaning.
7.) Remove the extension cord running through ceiling located next to the rear door.
8.) Remove the slide bolt locking devices from the rear door. (Main leaf only)
9.) Extension cords are to be for temporary use only.