Inspection History: FIRE - FINAL
Permit Number - T09OT01747
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2009 | FIRE - FINAL | Approved | ||
08/21/2009 | FIRE - FINAL | Denied | 1.) Need to make corrections on the violations noted. 2.) Still need to provide updated reports of the following: a.) Annuall sprinkler inspectionn report. b.) 5 year check valve inspection report. c.) Annual fire alarm inspection report. |
|
08/20/2009 | FIRE - FINAL | Denied | 1.) Replace all missing electrical cover plates. 2.) Need the updated annual sprinkler report.( last on file 9/11/07) 3.) Need the updated 5 yr. sprinkler inspection report.( last on file 12/11/03) 4.) Need the updated annual Fire Alarm report. ( last, not on file) 5.) Any and all deficiencies on either of the report must be corrected. |