Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/30/2009 FIRE - FINAL Approved PER INSP COPY
08/14/2009 FIRE - FINAL Denied 1.) Need approved floor plans. Must accurate and feet the buildinf foot print.
2.)Need an updated annual fire alarm inspection report.
3.) Provide directional exit signs directing to main exit frombreakroom area and from warehouse area.
4.) Extension cords are to be for temporary use only.
5.) Need at least 24 inches of clearance from the ceiling to top of any storage material.
6.) Need breaker blanks for the electrical panel located in the tool room.
7.) Need to maintain a clear and unobstructed area around electrical panels.
8.) Replace all missing cover plates.
9.) Cover all openings in ceilings
a.) warehouse area.
b.) breakroom area.