Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT01618
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2010 | FIRE - FINAL | Approved | Approved 3/10/10 | |
| 08/04/2009 | FIRE - FINAL | Denied | 1.) Need the current, accurate and approved(stamped) plans. Must reflect the building foot print. 2.) Annual sprinkler inspection is due at the end of thixs month. 3.) Need a copy of the updated 5 year check valve inspection report. 4.) Lable the door to the riser room,"RISER ROOM".4 inch high letters minimum. 5.) Unable to test the emergency back-up lights. 6.) Repair the ceiling tile located in the telephone room. 7.) Need a breaker blank in the electrical panel. 8.) Cover the opening in wall located in the electronics room. 9.) Need a cover plate in the small conference room. 10.) Portable extinguishers are due for annual inspection. |