Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2009 | FIRE - FINAL | Approved | ||
| 08/04/2009 | FIRE - FINAL | Denied | 1.) Screen door in the east front office area must be removed. 2.) Panic hardware for all gates to the enclosed area on the outside of building is required. 3.) Replace any missing cover plates. 4.) Cover all openings in walls and ceilings. 5.) All portable extinghuishers need service inspections. 6.) Secure lose cable hanging down between partitians and rear wall. 7.) Need to inspect the exterior room located on the east side of building.( locked at time of initial inspection) 8.) Need a thumb-turn lock on the inside portion of the swing door leading out from the kitchen area and into the main floor. 9.) Label (identify) breakers on electrical panel. |