Permit: T09OT01453

Parcel: 124051780


Addresses:

1118 E 6TH ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
07/28/2009 FIRE - FINAL Approved
07/17/2009 FIRE - FINAL Denied 1.) Need panic hardware for both exterior doors located in the main floor room area.
2.) Remove all door hardware off of the NE door, main floor. Must not have the appearence of a door.
3.) Extension cords are for temporary use only.
4.) Replace missing cover plates.
5.) Patio gate shall be locked in the open position when building is occupied. Failure to comply with this will require the installing of panic hardware on the gate.
6.) Wooden door leading out to the patio must be readily openable when building is occupied.
7.) Any door on the exit path shall be readily openable at all times.
8.) Re-locate "K" type extinguisher to a location 10 ft. minimum from closes hazard.