Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T09OT01412
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OK SIGN 2) BOND METAL ELBOW TO EQUIPMENT GROUND 3) SPLICES TO UNDERGROUND SPLICE BOX TO BE LISTED FOR WET LOCATION 4) SERVICE BELL BOX AT BLDG 5) GROUND BELL BOX AT BLDG 6) CLOSE OPEN KNOCKOUT BELL BOX AT BLDG 7) INSTALL COVER BELL BOX AT BLDG |