Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T09OT01405
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2009 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
07/16/2009 | CERTIFICATE OF OCCUPANCY | Partial Approval | IVRS - Inspection :* 1) WILL APPROVE WITH FIRE C OF O |
|
07/10/2009 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL BACK FLOW PREVENTER ON EAST EXTERIOR HOSE BIB 2) CAULK TOILETS AT FLOOR AND INSTALL KNOWLEDGE LEVER KNOBS ON BATHROOMS 3) NEED FIRE C OF O 4) ELECTRIC PANEL B NEEDS CIRCUIT BREAKER COVER 5) INSTALL DOOR TO REMAIN UNLOCKED WHILE BLDG OCCUPIED 6) YOU CANNOT HAVE PANIC HARDWARE AND DEAD BOLT ON SAME DOOR |