Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09OT01373

Parcel: 10821441A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09OT01373

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2009 FIRE - FINAL Approved
07/14/2009 FIRE - FINAL Denied In room 107 open work area correct sprinkler coverage. Heads to close together min of 6 feet apart, and heads can not be more than 7 foot 6 inches away from a wall. Will need a permit to relocate a sprinkler head.