Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/16/2009 |
FIRE - FINAL |
|
Approved |
|
| 07/14/2009 |
FIRE - FINAL |
|
Denied |
In room 107 open work area correct sprinkler coverage. Heads to close together min of 6 feet apart, and heads can not be more than 7 foot 6 inches away from a wall. Will need a permit to relocate a sprinkler head. |