Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT01373
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2009 | FIRE - FINAL | Approved | ||
07/14/2009 | FIRE - FINAL | Denied | In room 107 open work area correct sprinkler coverage. Heads to close together min of 6 feet apart, and heads can not be more than 7 foot 6 inches away from a wall. Will need a permit to relocate a sprinkler head. |