Permit: T09OT01314

Parcel: 12704222C


Addresses:

5002 E 4TH ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
08/11/2009 FIRE - FINAL Approved
07/07/2009 FIRE - FINAL Denied 1.) Emergency back-up lighting is burnt out.
a.) main door
b.) in fellowship hall.
2.) All permanent wiring must be installed per Electrical Code.
a.) ROMEX wiring up to 7 feet from floor must be protected within wall or electrical conduit.
aa.) closet, front lobby area.
bb.) closet, fellowship room area.

cc.) within the cluster of electrical wiring located behind the "SOUND" area.
3.) Open wiring.
a.) AV room
b.) Outside, SW corner of south wall.
4.) Provide a sign indicating not an exit on door in the "Fellowship" room leading into the "Prayer" room.
5.) Cover opening in wall located in the "Spare" room.
6.) Provide current Annual Fire Alarm inspection report.
7.) Need panic hardware for doors leading from the "Fellowship" room to the "Prayer" room to the exterior.