Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 07/15/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1) SIGN TO BE ON 20 AMP SIGN BRANCH CIRCUIT 2) NEED ACCESS TO XFMR 3) NEED GROUNDING ELECTRODE SYSTEM FOR XFMR 4) NEED TO HAVE PLANS AND PERMIT ON SITE 5) RECALL, WHEN READY AND LEAVE MESSAGE WITH CONTACT NAME & PHONE NUMBER |