Permit: T09OT01191

Parcel: 13013047E

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
07/08/2009 FIRE - FINAL Approved
06/12/2009 FIRE - FINAL Denied 1.) Need the 5 year check valve inspection report.
2.) Need address numbers for the building. Minimum of 12 inchs if building is 50 ft. or less from street. 15 inches if further then 50 ft.
3.) 2 sprinkler deflectors are obstructed by the A/C duct. Shorten the duct work or add or reposition sprinkler head.(plan and permits required)
4.) Replace all missing cover plates.
5.) Existing storage racks(unpermitted) in the process of being dismantled. If new tenent chooses to reinstall the racks, a permit will be required.