Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2009 | FIRE - FINAL | Approved | ||
| 06/18/2009 | FIRE - FINAL | Denied | 1.) In office and study room remove double cylinder keyed dead bolt locks and install thumb style dead bolt locks. 2.) Plans do not reflect what is on site i.e. narthex walls and doors remove 1 hour rating removed? 3.) Occupant. Load on approved plans dated 08/30/1960 states Occupant load of 200. To date plan review card states 326 occupant load therefore you will need to add an approved fire sprinkler system in the building or lower occupant load to 300. |