Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2009 | FIRE - FINAL | Approved | ||
| 06/03/2009 | FIRE - FINAL | Denied | 1.) Need a door knob for the front door. 2.) Large sliding doors at front of building must be kept open at all times when building is occupied. 3.) Large sliding doors located in the center of the room must be kept open at all times when the building is occupied. 4.) Secure all open junction boxes with cover plates. 5.) Secure/protect all ROMEX wiring that is below 7 feet in electrical conduit or behind a wall. 6.) Electrical wiring must be inspected by a certified electrictian. 7.) Repair the broken window in the back room area. 8.) Secure protruding bolts on the floor. Trip hazards. 9.) Unless occupant load is less then 50 occupants a.) a second exit door is required. b.) bothe doors must open in the direction of exit travel. c.) illuminated signs will be required. 10.) Must submit plans for fire approval. |