Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2009 | FIRE - FINAL | Approved | ||
| 07/15/2009 | FIRE - FINAL | Denied | IFC.906.2 Service repair Portable Fire Extinguishers X3. UFC.1027.5 Emergency 'Egress Lights' needs to be Serviced/repaired on East and West wall. IFC.703.1 Replace ceiling tiles in various locations of building. IFC.1011.2 'Exit Sign' at front door needs to be serviced/repaired. IFC.1008.1.8.3 Key lock on front door from egress side must be removed. 1008.1.9 'Panic Hardware' is required on front door. |