Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2010 | FIRE - FINAL | Approved | E-MAIL OF CITY WATER DEPT. STATED THEY SHOW A HYDRANT OUT FRONT OF PROPERTY. INSTALLED 1991 PER PLAN NUMBER 094-1991 AND LAST FLOW TEST WAS 2003. THEY SUSPECT SOMEONE HAS HIT THE HYDRANT AND COVERED PIPING UP. WATER WILL BE INSTALLING REPLACEMENT HYDRANT WITHIN 2 WEEKS. | |
| 04/12/2010 | FIRE - FINAL | Denied | 1.Fire hydrant to far away, on approved site plans show hydrant out front by road but no hydrant is there. Next hydrant is 260 feet to front gate. Hydrants shall be within 300 feet to farthest part of property with combustibles. 2. Need hydrants installed per plan or have plans changed by going through walk through again may be this will happen. |