Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2009 | FIRE - FINAL | Approved | APPROVED ON TI PERMIT BY LARRY IN JUNE. | |
| 04/24/2009 | FIRE - FINAL | Denied | 1.) Need illumunated Exit signs over the two required exit doors. 2.) Need Sign over main exit door that reads,"DOOR TO RMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". 3.) Need the updated annual sprinkler report. 4.) Need the updated 5 yr. check valve inspection report.(sprinkler system) 5.) Need updated annual Fire Alarm inspection report. 6.) Provide an exit sign over the door leading into the main warehouse area from the large storage room area. 7.) Remove slide-bolts from double doors located in the small storage room area. 8.) Breaker blanks for panel "B" and panel "Z". 9.) Remove double cylinder locks from all exterior doors exept the main door. Provide thumb-turn locks. 10.) Provide emergency back-up lighting for both required exits. 11.) Provide sign indicating the fire department connections. "FIRE DEPT. CONNECTIONS or FDC". must be visable from the street. |