Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2009 | FIRE - FINAL | Approved | ||
| 04/28/2009 | FIRE - FINAL | Denied | 1. Remove installation from sprinkler piping in warehouse. 2. Clear 30" inches around electrical transformer in warehouse. 3. Remove all LP tanks from inside building and store extra tanks outside in proper cage. Storage cage shall be 10' feet away from any openings into building and no smoking within 10' feet of storage cage. 4. Correct sprinkler coverage in storage room back warehouse, sprinkler head 8' feet off wall was a office now a storage room. 5. Need up to date fire sprinkler inspection and 5 year alarm check valve inspection done. |