Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT00697
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2009 | FIRE - FINAL | Approved | ||
04/14/2009 | FIRE - FINAL | Denied | 1.) Need address numbers.Must be minimum of 12 inches high. 2.) Door in the hallway area between the offices and the warehouse area sticks and is hard to open. 3.) The ROMEX wiring located next to the north end roll-up doors in tne warehouse area must be protected in conduit. 4.) Secure loose wiring located on the ceiling area next to the south end roll-up doors. 5.) Secure open wiring in box located next to the electrical panel, warehouse area. 6.) Provide a KNOX-BOX and keys for property and building access. 7.) Secure the flood light hanging by electrical wiring located outside on the metal Ramada. 8.) Remove the combination locking device from the hallway door. |