Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2009 | FIRE - FINAL | Approved | ||
| 04/01/2009 | FIRE - FINAL | Denied | Not approved 4/1/09. 1.) Need updated approved plans. Plans provided do not match building foot print. 2.) Need address numbers for building. Must face 22nd. St. 3.) Make repairs to the SW exit door. Loose hinges. 4.) Remove one of the locks from the same door. Only one locking device per door is allowed. 5.) Provide a door knob for the SE exit door. 6.) Need cover plate open wiring outside torear of building. |