Inspection History Details
Inspection Status: Closed
Inspection History: SIGN ELECTRIC
Permit Number - T09OT00541
Inspection Description - SIGN ELECTRIC
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2010 | SIGN ELECTRIC | Closed | ELEC REMOVED FROM PERMIT AT THIS TIME | |
11/03/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH PREVIOUS INSPECTION REQUEST 2) GROUND ROD CUT, NEED GROUNDING ELECTRODE SYSTEM PER NEC 250 3) GROUND CLAMP LISTED FOR ONE WIRE TERMINATION 4) IT APPEARS THERE ARE NO DISCONNECTING MEANS OR OVER CURRENT PROTECTION FOR SYSTEM 5) DC TO AC INVERTER APPEARS TO BE UN-LISTED EQUIPMENT |
|
05/26/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO PROVIDE POWER TO SIGN THAT MEETS ALL REQUIREMENTS OF 2005 NEC TO USE SOLAR POWER NEED TO PROVIDE PLANS TO CITY AND USE LISTED EQUIPMENT. SIGN NOT TO BE ENERGIZED UNTIL ALL ELECTRIC IS INSPECTED AND PASSED. DISCONNECT ALL XLAN CODE COMPLIANT ELECTRIC. HAVE QUALIFIED ELECTRICAL CONTRACTOR DO ALL NEW WORK. 2. OK SIGN 3. RECALL WHEN READY |