Permit: T09OT00539

Parcel: 141114100


Addresses:

7850 S RITA RD

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
04/08/2009 SIGN ELECTRIC Approved IVRS - Inspection :*
04/07/2009 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
03/27/2009 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
03/26/2009 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/25/2009 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
1. SIGNS TO BE ON OWN 20 AMP DEDICATED CIRCUIT
NEC 600.5
2. NEED TO HAVE PROPER WORKING CLEARANCES IN FRONT OF PANELS NEED TO REMOVE CASES OF SODA & GATORADE
NEC 110.26
3. LABEL CIRCUIT IN PANEL FOR SIGN CIRCUIT