04/08/2009 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
04/07/2009 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* | |
03/27/2009 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* | |
03/26/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/25/2009 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1. SIGNS TO BE ON OWN 20 AMP DEDICATED CIRCUIT NEC 600.5 2. NEED TO HAVE PROPER WORKING CLEARANCES IN FRONT OF PANELS NEED TO REMOVE CASES OF SODA & GATORADE NEC 110.26 3. LABEL CIRCUIT IN PANEL FOR SIGN CIRCUIT |