Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09OT00512

Parcel: 10511061P


Addresses:

4510 N ORACLE RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09OT00512

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2010 FIRE - FINAL Approved THESE INSPECTIONS COMPLETED UNDER SUBSEQUENT PERMITS AND FIELD VISITS
03/16/2009 FIRE - FINAL Partial Approval TEMP C OF O OK
1. Correct sprinkler coverage by west entrance heads to close.
2. Need up to date fire sprinkler inspection done. This is done yearly, last report on file 10/28/2007.
3. Need up to date 5yr alarm check valve inspection, nothing on file.
4. Correct sprinkler coverage in the following areas and correct any deficiencies found on sprinkler reports:
a. Coverage in cash wrap storage room
b. By front court entrance sales floor area, heads to far off wall.
c. Receiving department under stock shelves
d. Top (3rd floor) uprights storage area.
e. 2nd floor storage northwest area uprights not 130sq. coverage
f. 2nd floor east dressing room outside door
g. Water motor gong not working repair or replace or repair and replace electrical water flow bell.
5. Clear all stock out of east exit hallway, repair lighting for egress exiting and repair back up lighting to exit sign and egress lighting.
6. After checking all exits shall clear all trash and stock from all exit ways and keep clear at all times.
7. Need a report on emergency generator showing all is good with back up lighting, exit signs for store and maintenance for generator.