Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T09OT00389
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2009 | FIRE - FINAL | Denied | Locks, holds and notices noted. 1.) Provide illuminated eit signs over both of the required exits. 2.) Provide emergency back-up lighting for both required exits. 3.) Signage over both exit doors that reads: "DOOR MUST REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" 4.) Only approved adaptors are allowed for use. 5.) Extension cords are to be for temporary use only. 6.) Provide a "NOT AN EXIT" sign for the NW exterior door. 7.) Directional Exit signs must be provided to direct towards the exit doors in areas where the xit door is not plainly visable. 8.) Maintain a 30-36 inch isle for exit access. |