Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT00325
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2009 | FIRE - FINAL | Approved | PER INSP CARD | |
07/07/2009 | FIRE - FINAL | Cancelled | ||
02/23/2009 | FIRE - FINAL | Denied | 1. NEED UP TO DATE FIRE SPRINKLER INSPECTION FOR BASEMENT, LAST REPORT ON FILE 10/31/2007. THIS IS DONE YEARLY. 2. NEED UP TO DATE 5 YEAR FIRE ALARM CHECK VALVE INSPECTION DONE, LAST REPORT ON FILE 11/30/2001. 3. FOYER MUST BE 1 HOUR RATED, WITH 20 MIN. FIRE DOORS TO MEET EXITING REQUIRMENTS. 1027.17 4. MEANS OF EGRESS ILLUMINATION SHALL BE AT 1 FOOT CANDLE POWER AT WALKING SURFACE LEVEL. 1006 |