Permit: T09OT00325

Parcel: 11703306A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09OT00325

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2009 FIRE - FINAL Approved PER INSP CARD
07/07/2009 FIRE - FINAL Cancelled
02/23/2009 FIRE - FINAL Denied 1. NEED UP TO DATE FIRE SPRINKLER INSPECTION FOR BASEMENT, LAST REPORT ON FILE 10/31/2007. THIS IS DONE YEARLY.
2. NEED UP TO DATE 5 YEAR FIRE ALARM CHECK VALVE INSPECTION DONE, LAST REPORT ON FILE 11/30/2001.
3. FOYER MUST BE 1 HOUR RATED, WITH 20 MIN. FIRE DOORS TO MEET EXITING REQUIRMENTS. 1027.17
4. MEANS OF EGRESS ILLUMINATION SHALL BE AT 1 FOOT CANDLE POWER AT WALKING SURFACE LEVEL. 1006