Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT00312
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2009 | FIRE - FINAL | Approved | ||
02/19/2009 | FIRE - FINAL | Denied | 1.) Extension cords not be a substitute for permanent wiring. To be for temporary use ony. 2.) Emergency back-up lights in the cubicle area are not working. 3.) Spliced wiring is prohibioted. (conference room) 4.) Re-locate exit sign between the office area and the warehouse. Relocate to opposite side of door. 5.) Rear exit door must be readily openable without the use of a key, special knowledgeor special effort. 6.) Lable door to electrical room "ELECTRICAL or ELECTRICAL PANEL" 7.) Povide a clean area around the electrical panel. |