Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T09OT00267

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
06/03/2009 SIGN ELECTRIC Approved
05/29/2009 SIGN ELECTRIC Partial Approval IVRS - Inspection :*
NEED TO OBTAIN FROM DEVELOPMENT SERVICES THE 09815 ACTIVITY ADDED TO PERMIT AND PAY ADDITIONAL FEES
RECALL AFTER

OK SIGNS ON SITE
05/18/2009 SIGN ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ADD SIGN SHOP TO INSPECTION CARD
2. MARKING LABELS NEEDED 600.4
3. SERVICE WALKWAY TO SIGN EQUIPMENT NEEDED 600.21
4. MANUFACTURE CALLS FOR SPECIFIC TYPE CABLE & MODELS
5. GROUNDING CONDUCTOR TO BE 14GA MIN
6. SUPPORT LV CABLES
7. USE APPROVED MOUNTING HARDWARE - NOT WOOD OR DRYWALL SCREWS
8. PLEASE VERIFY LISTING IN SAM FOR LED MODULES