Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2009 | SIGN ELECTRIC | Approved | IVRS - Inspection :* 1) OK SIGNS |
|
| 06/17/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH #3, 5, 7 |
|
| 06/09/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND LED LETTERS AND CABINETS 2. SWITCHES TO BE EXTERNAL 3. POWER SUPPLIES AND ELECTRIC BOXES TO BE ACCESSIBLE 4. SWITCHES TO BE CAPABLE TO BE LOCKED 5. GROUND JUNCTION BOXES 6. MAINTAIN CLEARANCES FOR HEAT OF POWER SUPPLIES 7. MISSING JUNCTION BOX COVERS |
|
| 05/29/2009 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* PLEASE PROVIDE ACCESS TO SIGNS |