Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT00169
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2009 | FIRE - FINAL | Approved | ||
| 04/24/2009 | FIRE - FINAL | Denied | 1.) Install Fire Department key system. (Knox-Box) 2.) Make the two single doors locarted in the rear storage shed readily openable from the inside. 3.) Provide sign for double door located in rear storage shed indicating that it is not an exit. Per Fire Department standards, OK for electrical reconnection. |
|
| 03/04/2009 | FIRE - FINAL | Denied | 1.) Install fire dept. key system for access on property. 2.) Weather proof outlets on parking lot lights both north and south end. Cover plates needed on wring hanging out of parking light poles. 3.) All wiring below 7' shall be protected with wall or install in conduit; storage shed back of building correct wiring or remove wiring. 4.) Correct conduit on back of building falling off wall. 5.) Properly wire hot water heater to electrical Code standards. 6.) Back garage properly wire lights on ceiling; to electrical code standards. |