Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT00002
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2009 | FIRE - FINAL | Approved | ||
02/23/2009 | FIRE - FINAL | Not ready for Inspection | NEED BATTERY BACK UP LIGHTING IN THE BACK SECTION. ONE FOOT CANDLE POWER TO FLOOR. | |
01/22/2009 | FIRE - FINAL | Not ready for Inspection | ||
01/21/2009 | FIRE - FINAL | Denied | 1. Need up to date fire sprinkler inspection done, last inspection on file 09/26/2006. This is done yearly. 2. Need up to date fire alarm check valve inspection done, this is done every five years. Last one on file 12/05/1997. 3. Correct sprinkler coverage in back room heads to close by old bathroom that was removed and heads to far off wall 8 foot 8 inches. Will need permit to do this work. 4. Install 120V and battery back exit signs and lighting over both rear exit door and front door and on wall over door from front to rear room. 5. Remove cross bar locks on both rear exits. Only use approved type hardware. |