Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* 1) MOVE ROCKS IN FRONT OF PANEL CLEAR TO FENCE |
|
| 09/24/2009 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SERVICE CONDUCTOR TO BE PER 230.24 OVER PUBLIC ROADWAY 2) MAINTAIN BENDING RADIUS OF CONDUCTORS 3) IDENTIFY GROUNDED CONDUCTOR AT LUG TERMINATION 4) MAINTAIN WORKING CLEARANCES 110.26 |