Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/01/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/11/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
1. SERVICE RECEPTACLE NOT PROPERLY WIRED, PROVIDE DEDICATED CIRCUIT
2. ITEMS 5, 6, 8, 9, 12, 13, DATED 1/27/10 HAVE NOT BEEN CORRECTED, CONTRACTOR WILL BE ON SITE FOR NEXT INSPECTION OR A RE-FEE WILL BE ATTACHED TO PERMIT
01/27/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRICAL CONDUIT NEEDS ROOF JACK AT ROOF PENETRAION
2) ELECTRICAL CONDUIT FITTINGS NOT PROPERLY INSTALLED
3) EELCTRICAL CONDUIT NEEDS TO BE BLOCKED UP OFF OF ROOF
4) PVC JOINTS TO HAVE PRIMER, PRIMER IS TO BE PURPLE IN COLOR
5) PVC IS TO BE WEATHER COATED
6) PVC IS TO BE BLOCKED UP OFF OF ROOF AT MAX 4' SPACING
7) PVC IS TO TERMINATE 6" ABOVE GRADE
8) SEAL ALL DUCT JOINTS
9) DUCT SWITCH FITTING DOES NOT APPEAR TO PROVIDE ENOUGH VOLUMN FOR AIR FLOW (HIGH SPEED)
10) PROVIDE CONDUIT FOR LOW VOLTAGE CONTROL WIRING
11) SEAL HOLES IN DUCT
12) PROVIDE BAROMETRIC DAMPER OR OTHER MEANS OF SEPERATING EVAP COOLER FROM A/C UNIT
13) PROVIDE GFI SERVICE RECEPT WITHIN 25' OF R.T.U.
14) DO NOT USE NEUTRAL WIRE AS HOT LEG
15) BREAKER IN PANEL NOT LABELED