Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/11/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : 1. SERVICE RECEPTACLE NOT PROPERLY WIRED, PROVIDE DEDICATED CIRCUIT 2. ITEMS 5, 6, 8, 9, 12, 13, DATED 1/27/10 HAVE NOT BEEN CORRECTED, CONTRACTOR WILL BE ON SITE FOR NEXT INSPECTION OR A RE-FEE WILL BE ATTACHED TO PERMIT |
|
| 01/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRICAL CONDUIT NEEDS ROOF JACK AT ROOF PENETRAION 2) ELECTRICAL CONDUIT FITTINGS NOT PROPERLY INSTALLED 3) EELCTRICAL CONDUIT NEEDS TO BE BLOCKED UP OFF OF ROOF 4) PVC JOINTS TO HAVE PRIMER, PRIMER IS TO BE PURPLE IN COLOR 5) PVC IS TO BE WEATHER COATED 6) PVC IS TO BE BLOCKED UP OFF OF ROOF AT MAX 4' SPACING 7) PVC IS TO TERMINATE 6" ABOVE GRADE 8) SEAL ALL DUCT JOINTS 9) DUCT SWITCH FITTING DOES NOT APPEAR TO PROVIDE ENOUGH VOLUMN FOR AIR FLOW (HIGH SPEED) 10) PROVIDE CONDUIT FOR LOW VOLTAGE CONTROL WIRING 11) SEAL HOLES IN DUCT 12) PROVIDE BAROMETRIC DAMPER OR OTHER MEANS OF SEPERATING EVAP COOLER FROM A/C UNIT 13) PROVIDE GFI SERVICE RECEPT WITHIN 25' OF R.T.U. 14) DO NOT USE NEUTRAL WIRE AS HOT LEG 15) BREAKER IN PANEL NOT LABELED |