Permit: T09ME00792

Parcel: 10612129A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09ME00792

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/18/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
12/18/2009 MECHANICAL - FINAL Cancelled CANCELLED PER CONTRACTOR CUMMINGS PLUMBING #293-6900 AT 12:56 PM VIA TELEPHONE CALL
12/15/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLEX DUCT UNDER TRAILER TO BE MIN. R-8
2) FLEX DUCT UNDER TRAILER TO BE SUPPORTED OFF OF GROUND A MIN. OF 4"
3) NEUTRAL WIRE CANNOT BE USED AS AT NOT LEG.
4) SEAL TITE TO BE BLOCKED UP OFF OF GROUND MIN. 1.5"
5) PROVIDE 110V SERVICE OUTLET WITHIN 25' OF UNIT
6) PROVIDE OPEN ACCESS UNDER TRAILER AT UNIT AREA FOR COMPLETE INSPECTION