Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/18/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/18/2009 | MECHANICAL - FINAL | Cancelled | CANCELLED PER CONTRACTOR CUMMINGS PLUMBING #293-6900 AT 12:56 PM VIA TELEPHONE CALL | |
| 12/15/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX DUCT UNDER TRAILER TO BE MIN. R-8 2) FLEX DUCT UNDER TRAILER TO BE SUPPORTED OFF OF GROUND A MIN. OF 4" 3) NEUTRAL WIRE CANNOT BE USED AS AT NOT LEG. 4) SEAL TITE TO BE BLOCKED UP OFF OF GROUND MIN. 1.5" 5) PROVIDE 110V SERVICE OUTLET WITHIN 25' OF UNIT 6) PROVIDE OPEN ACCESS UNDER TRAILER AT UNIT AREA FOR COMPLETE INSPECTION |