Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09ME00781

Parcel: 130123380


Addresses:

3539 E 32ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/23/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/18/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SEDIMENT TRAP AT GAS PIPING TO UNIT
2) PROVIDE NEW LABELED GAS FLEX TO UNIT
3) ALL FLUE (SINGLE WALL) JOINTS TO HAVE A MINIMUM 3 SCREWS, NO TAPE
4) SUPPLY DUCT IS TO BE INSULATED