Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/22/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE PIECE OF VENT PIPE USED TO EXTEND VENT IS INSTALLED UPSIDE DOWN AND DOES NOT MATCH THE EXISTING VENT PIPE |
|
| 12/15/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSOR OVERFUSED-40 AMP IS MAX 2) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE ON ROOF 3) EVERYTHING ELSE IS OK |