Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/09/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE LADDER TO ACCESS ROOF |
|
| 11/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE HAVE VICTOR RESCHEDULE AFTER THANKSGIVING |
|
| 11/19/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAKE ALL CORRECTIONS AND RECALL FOR FINAL |
|
| 11/17/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A/C UNIT NOT FUSED CORRECTLY 2) DO NOT USE TAPE TO SEAL INSIDE THE DUCT CONNECTIONS TO UNIT 3) USE DUCT SEALER 4) USE SHEET METAL TO BLANK OFF PLENIUMS NOT SIZED CORRECTLY, NOT TAPE 5) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 6) OK TO TERMINATE INTO THE RAIN GUTTER AND DOWNS SPOUT 7) USE ONLY REDWOOD OR PRESSURE TREATED WOOD UNDER ANGLE IRON FRAME 8) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 9) PAINT EXPOSED PVC WITH LATEX PAINT 10) BLOCK AND CLAMP PVC EVER 4' 11) SECURE ELECTRIC CONDUIT 12) SEAL ALL JOINTS OF EXPOSED DUCT |