Permit: T09ME00732

Parcel: 114460570


Addresses:

7190 E ONDA CI

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/21/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/09/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LADDER TO ACCESS ROOF
11/20/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE HAVE VICTOR RESCHEDULE AFTER THANKSGIVING
11/19/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) MAKE ALL CORRECTIONS AND RECALL FOR FINAL
11/17/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A/C UNIT NOT FUSED CORRECTLY
2) DO NOT USE TAPE TO SEAL INSIDE THE DUCT CONNECTIONS TO UNIT
3) USE DUCT SEALER
4) USE SHEET METAL TO BLANK OFF PLENIUMS NOT SIZED CORRECTLY, NOT TAPE
5) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
6) OK TO TERMINATE INTO THE RAIN GUTTER AND DOWNS SPOUT
7) USE ONLY REDWOOD OR PRESSURE TREATED WOOD UNDER ANGLE IRON FRAME
8) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
9) PAINT EXPOSED PVC WITH LATEX PAINT
10) BLOCK AND CLAMP PVC EVER 4'
11) SECURE ELECTRIC CONDUIT
12) SEAL ALL JOINTS OF EXPOSED DUCT