Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2010 | MECHANICAL - INTERMEDIATE | Approved | ||
| 05/20/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET. CAP OFF VENT UNDER RETURN PLATFORM OR EXTEND ABOVE DRAIN PAN. USE PURPLE PRIMER ON ALL PVC FITTINGS 2) MAKE UNIT DATA PLATE WITH THE PROPER HEAT STRIP INSTALLED AND PROVIDE PROPER OVER CURRENT PROTECTION 3) PROVIDE A BUSHING WHERE ELECTRIC WIRE ISNIDE FAN COIL PASSES THRU PARTITIONS 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT THE CONDENSOR |
|
| 05/19/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |