Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 02/09/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SUPPORT UNDER GAS LINE AND ELECTRIC CONDUIT 2) PROVIDE A TRAP ON CONDENSATE DRAIN LINE PER INSTALL INSTRUCTIONS 3) PAINT EXPOSED PVC WITH LATEX PAINT 4) USE PURPLE PRIMER PRIOR TO GLUING PVC FITTINGS 5) USE RED WOOD OR PRESSURE TREATED WOOD FOR ALL EXPOSED SUPPORTS 6) GAS LINE CANNOT BE INCREASED FROM 1/2" TO 3/4" 7) RELOCATE ELECTRIC DISCONNECT AWAY FROM FLUE DISCHARGE WHICH IS CAUSING CONDENSATION INSIDE DISCONNECT 8) PROVIDE THE REQUIRED DRAWING TO ALLOW A NEW A/C ON THE ROOF 9) SERVICE RECEPT HAS NO POWER 10) RECEPT CANNOT BE ON A SWITCH 11) USE ONLY A SIEMENS BREAKER FOR A/C UNIT |